DSP SOLAR HOME UPS 
MODEL SSW-750 SSW-1050 SSW-2000 SSW-3500 SSW-5000 SSW-6000
CHARGE CONTROLLER 12V / 30A 12V / 50A 24V / 50A 48V / 50A 48V / 50A 96V / 50A
SOLAR PANEL 500W 600W 1500W 3000W 4000W 5000W

 

MODELS & TECHNICAL CHART
MODEL SSW-750 SSW-1050 SSW-2000 SSW-3500 SSW-5000 SSW-6000
NOMINAL BATTERY VOLTAGE 12V / 30A 12V / 50A 24V / 50A 48V / 50A 48V / 50A 96V / 50A
Solar Panel Connected 500W 600W 1500W 3000W 4000W 5000W
AC MAINS MODE
Input Voltage Range (Normal Mode) 110 to 290 VAC ± 10 VAC (Wide Range)
Input Voltage Range (UPS Mode) 170 to 260 VAC ± 5VAC
Changeover Time Maximum < 30 ms (in Normal Mode) and < 10 ms (in UPS Mode)
Max. Charging Current (NC) 10A ± 1A
Max. Charging Current (HC) 12A ± 1A
Boost Charging Voltage 14.2±0.2 VDC 28.4±0.2 VDC 56.8±0.2 VDC 113.6±0.2
VDC
142.0±0.2
VDC
213.0±0.2
VDC
Float Charging Voltage 13.8±0.2 VDC 27.6±0.2 VDC 55.2±0.2 VDC 110.4±0.2
VDC
138.0±0.2
VDC
207.0±0.2
VDC
BATTERY BACKUP MODE
Output Voltage at No Load 230 VAC ± 5 VAC
Output Frequency 50.0Hz ± 0.5Hz
Pwer Factor 0.8 lag to Unity
Output Wave Form (At No Load) 100% Pure Sine Wave
Battery Low alarm 10.4±0.2 VDC 20.8±0.2 VDC 41.6±0.2 VDC 83.2±0.2
VDC
104.0±0.2
VDC
156.0±0.2
VDC
Battery Low protection 10.2±0.2 VDC 20.4±0.2 VDC 40.8±0.2 VDC 81.6±0.2
VDC
102.0±0.2
VDC
153.0±0.2
VDC
Overload (Normal/ UPS) 120%
Short Circuit (Normal/ UPS)                                                        300%

 

Benefits of Digital Home UPS

  • Low charging & Hi-charging option as per need of customer
  • Software controlled pulse charging
  • Enhances battery life due to smart charger
  • We strongly recommend the usage of Tubular Battery with Inverter for excellent backup & extra long battery life